Smallest standard AWG that meets both the voltage-drop limit and the NEC ampacity limit
Cross-sectional area2.92mm^2
Actual voltage drop3.18V
Voltage drop2.65%
Wire resistance0.1588ohm
Wire ampacity25A
Wire diameter2.053mm
2.65 %
NEC branch limit (3%)<3NEC feeder limit (5%)3-5Excessive drop5+
▸
Use AWG 12 for this circuit.
The voltage drop of 2.65% is within the NEC-recommended 3% for branch circuits.
AWG 12 has an ampacity of 25 A at the selected insulation rating, giving 5 A of headroom above your load.
Always size wire to the larger of the voltage-drop result and the NEC ampacity limit - this calculator does that automatically for copper and aluminum.
Next stepVerify that your circuit breaker rating does not exceed the ampacity of the wire you select.