220 Volt Wire Size Calculator
Enter your load current, the one-way wire run length, conductor material, and the maximum voltage drop you will accept. The calculator picks the smallest AWG gauge that satisfies both the NEC ampacity requirement and your voltage-drop limit, then shows the actual expected voltage drop and wire dimensions.
How wire size is determined for 220V circuits
Selecting the correct wire gauge for a 220V (240V) circuit comes down to two independent limits: ampacity and voltage drop. Ampacity is the maximum current a wire can carry continuously without overheating, set by NEC Table 310.15(B)(16) based on conductor material, insulation temperature rating, and installation method. Voltage drop is the reduction in voltage along the run caused by the wire's resistance - it limits how long the run can be before the appliance receives noticeably less than 220V. The correct gauge is whichever is larger (lower AWG number) of the two independent requirements.
NEC 80% continuous-load rule
For a continuous load (one that runs for three or more hours at a time - such as a water heater, EV charger, or HVAC unit), NEC Section 210.19(A) requires the conductor to be sized at 125% of the load current. In practice this means if your appliance draws 30 A, you design for 37.5 A. This is the same as saying the breaker should only be loaded to 80% of its rating. The calculator applies this factor automatically when you select "continuous load." For short-duration loads such as a table saw or welding machine, you can deselect it.
Voltage drop formula and acceptable limits
The NEC recommends keeping voltage drop to no more than 3% on a branch circuit and 5% total (feeder plus branch combined). For a 220V circuit, 3% equals 6.6 V. The formula for required cross-sectional area is: A = 2 x rho x L x I / (V x drop_fraction), where rho is the resistivity of the conductor (1.724e-8 ohm-m for copper, 2.655e-8 for aluminum), L is the one-way run length in metres, I is the current in amps, V is 220 V, and drop_fraction is 0.03 for 3%. The factor of 2 accounts for the round-trip path (hot and neutral). Once you have the required area, convert it to the next standard AWG size that meets or exceeds that area.
Copper vs aluminum wiring
Copper is the most common choice for branch circuits because it has lower resistivity (better conductivity), is easier to terminate, and does not oxidize as readily. Aluminum is lighter and cheaper per foot, making it practical for service entrance conductors and large feeder runs. For the same ampacity, aluminum requires roughly one AWG step larger than copper (for example, 6 AWG aluminum vs 8 AWG copper at 50 A). When using aluminum wiring, all connections must use anti-oxidant compound and fittings rated for aluminum (marked AL-CU or AL). Consult a licensed electrician before installing aluminum branch circuits in residential buildings - many local codes restrict or require special procedures for it.
Common 220/240V wire sizes (NEC 75 C, limited by 240.4(D))
| AWG | Copper limit (A) | Aluminum limit (A) | Area (mm²) | Diameter (mm) |
|---|---|---|---|---|
| 14 AWG | 15 | N/A | 2.08 | 1.63 |
| 12 AWG | 20 | 15 | 3.31 | 2.05 |
| 10 AWG | 30 | 25 | 5.26 | 2.59 |
| 8 AWG | 50 | 40 | 8.37 | 3.26 |
| 6 AWG | 65 | 50 | 13.3 | 4.11 |
| 4 AWG | 85 | 65 | 21.1 | 5.19 |
| 3 AWG | 100 | 75 | 26.7 | 5.83 |
| 2 AWG | 115 | 90 | 33.6 | 6.54 |
| 1 AWG | 130 | 100 | 42.4 | 7.35 |
| 1/0 AWG | 150 | 120 | 53.5 | 8.25 |
NEC Table 310.16 ampacity for conductors in conduit at 75 C. For 14, 12 and 10 AWG the binding limit is the small-conductor rule in NEC 240.4(D) (15/20/30 A copper, 15/25 A aluminum), which is shown here. Apply the 125% factor for continuous loads before choosing a gauge.
Frequently asked questions
What wire size do I need for a 30-amp 220V circuit?
A 30-amp 220V circuit typically requires 10 AWG copper wire for runs up to about 100 feet with less than 3% voltage drop. For longer runs or continuous loads (where the NEC 125% factor applies), upgrade to 8 AWG. Use the calculator above to confirm for your exact run length and whether the load is continuous.
Can I use aluminum wire for a 220V circuit?
Yes, aluminum conductors are code-compliant for 220V circuits when properly installed. They require anti-oxidant compound at all terminations, connectors and breakers rated for aluminum (marked AL or AL-CU), and proper torque at connections. Aluminum is one AWG size larger than copper for the same ampacity - use 6 AWG aluminum where you would use 8 AWG copper, for example.
What does voltage drop mean and why does it matter?
Voltage drop is the reduction in voltage between the panel and the load, caused by the resistance of the wire. A 3% drop on a 220V circuit means the appliance receives only about 213.4 V instead of 220 V. Excessive voltage drop reduces motor efficiency, causes lights to dim, and can damage electronics. The NEC recommends a maximum of 3% on a branch circuit and 5% combined for the feeder and branch circuit together.
What is the NEC 80% rule for wire sizing?
For any load that operates continuously (3 hours or more), NEC Section 210.19(A) requires the conductor to be rated at 125% of the load current (the same as limiting the actual load to 80% of the wire's rated capacity). For example, a 30 A continuous load requires a conductor and breaker rated for 37.5 A, so you would use a 40 A breaker and wire sized for 40 A. This protects the insulation from long-duration heat.
Does the voltage matter for wire sizing?
Voltage matters indirectly for voltage-drop calculations but not for ampacity. The ampacity of a wire (how many amps it can carry safely) depends only on the conductor material, gauge, insulation rating, and ambient temperature - not on whether the circuit is 120V or 220V. Voltage becomes relevant when calculating how many volts are lost over a long run at a given current.