3-Phase Motor Amperage Calculator

Enter your motor power rating, supply voltage, efficiency, and power factor to find the full-load current (FLA) for any 3-phase AC motor. The calculator also shows the starting current (LRA), the minimum conductor AWG size per NEC guidelines, and the recommended circuit breaker rating. Switch between horsepower and kilowatts, and choose your line voltage from common industrial standards or enter a custom value. All results update instantly.

Your details

The rated output power printed on the motor nameplate.
hp
Select the line-to-line supply voltage, or choose Custom to enter a specific value.
Nameplate efficiency as a percentage. Premium-efficiency motors typically fall between 88% and 96%.
%
Ratio of real power to apparent power (dimensionless, 0 to 1). Typical 3-phase induction motors run 0.80 to 0.92 at full load.
Locked-rotor current as a multiple of FLA. Typical induction motors draw 6 to 8 times FLA at start (DOL). Use lower values for soft starters or VFDs.
Full-load amperage (FLA)Medium motor (10-50 A)
11.97A

Steady-state current at rated load

Starting current (LRA)71.8A
Min. conductor size14 AWG
Circuit breaker rating30A
Apparent power (kVA)9.54kVA
Real power input (kW)8.11kW
Full-load (FLA)11.97
Starting (LRA)71.8
Breaker max30
07.4814.96063125
Load (%)
Amperes (A)
Load (%)Current (A) vs Load
00
50.6
101.2
151.8
202.39
252.99
303.59
354.19
404.79
455.39
505.98
556.58
607.18
657.78
708.38
758.98
809.57
8510.17
9010.77
9511.37
10011.97
10512.57
11013.17
11513.76
12014.36
12514.96

Full-load amperage: 11.97 A at 460 V

  • At 460 V line-to-line and 92% efficiency, your 10 hp motor draws about 11.97 A at full load.
  • The locked-rotor starting current is approximately 71.8 A -- plan your branch circuit accordingly.
  • NEC 430.52 allows a maximum inverse-time circuit breaker of 30 A (250% of FLA). Always verify with your AHJ and the motor nameplate.

Next stepCross-check this FLA against the motor nameplate. The actual rated current can differ from the calculated value due to motor design variations. Always size conductors and protective devices to the nameplate FLA, not the estimated value.

What is 3-phase motor full-load amperage?

Full-load amperage (FLA) is the current a motor draws from the supply lines when it operates at its rated output power, rated voltage, and rated frequency. It is the fundamental number for sizing branch-circuit conductors, protective devices, starter contacts, and disconnect switches. Every 3-phase induction motor carries its rated FLA on the nameplate; this calculator estimates that value from the nameplate power rating when the actual current figure is not available.

The 3-phase motor amperage formula

For a balanced 3-phase system using line-to-line voltage, the full-load current is: I = P_input / (sqrt(3) x V_L x PF), where P_input is the electrical real power drawn from the supply in watts, V_L is the line-to-line voltage, and PF is the power factor. Because motors convert electrical energy with less than 100% efficiency, the electrical input exceeds the mechanical output: P_input = P_output / eta, where eta is efficiency expressed as a decimal. Substituting: I = P_output / (sqrt(3) x V_L x PF x eta). For power given in horsepower, multiply by 745.7 to convert to watts first.

NEC conductor and overcurrent protection sizing

The National Electrical Code (NEC) Article 430 sets the rules for motor branch circuits in the United States. Conductors must be rated for at least 125% of the motor FLA (NEC 430.22), which guards against continuous heat buildup. The maximum inverse-time circuit breaker is 250% of FLA (NEC 430.52 Table 430.52), while time-delay fuses can be sized at up to 175%, and non-time-delay fuses at up to 300%. Overload relays are set at 115% to 125% of nameplate FLA. These rules apply to standard squirrel-cage induction motors; wound-rotor, DC, and hermetic refrigerant compressor motors have separate tables. Always verify with your authority having jurisdiction (AHJ).

Starting current and motor protection considerations

When a squirrel-cage induction motor starts across the line (direct-on-line, or DOL), it draws 6 to 8 times its rated FLA for the first few seconds until it accelerates to speed. This locked-rotor amperage (LRA) determines the minimum interrupt capacity of the overcurrent device and influences the voltage dip the supply system experiences. Soft starters reduce LRA to roughly 3 to 4 times FLA by ramping the voltage, while variable-frequency drives (VFDs) can limit starting current to about 1 to 1.5 times FLA. For motors in buildings or on shared services, consult the demand constraints before sizing purely to NEC minimums.

Typical full-load currents - 3-phase AC motors at 460 V (NEC Table 430.250)

Motor HPFLA at 460 V (A)FLA at 208 V (A)FLA at 230 V (A)
0.51.12.42.2
0.751.63.53.2
12.14.64.2
1.536.66
23.47.56.8
34.810.69.6
57.616.715.2
7.51124.222
101430.828
152146.242
202759.454
253474.868
30408880
4052114.4104
5065143130
6077169.4154
7596211.2192
100124272.8248

Approximate full-load amperage for standard squirrel-cage induction motors at 460 V, 60 Hz, per NEC 2023 Table 430.250. Actual values depend on motor design -- always use the nameplate.

Frequently asked questions

How do I calculate the amperage of a 3-phase motor?

Use the formula I = P / (1.732 x V x PF x eta), where P is the rated output power in watts (multiply horsepower by 745.7 first), V is the line-to-line voltage, PF is the power factor, and eta is the efficiency as a decimal. For example, a 10 hp motor at 460 V with 92% efficiency and 0.85 power factor: I = (10 x 745.7) / (1.732 x 460 x 0.85 x 0.92) = 7457 / 621 = approximately 12.0 A.

What is the difference between FLA and LRA?

Full-load amperage (FLA) is the steady-state current drawn when the motor operates at its rated horsepower. Locked-rotor amperage (LRA), also called starting current, is the momentary current drawn when the motor shaft is stationary and the rotor has not yet begun to turn. For standard induction motors, LRA is typically 6 to 8 times FLA. Conductors are sized to the FLA; protective devices must withstand the LRA without nuisance tripping.

What voltage should I use in the formula -- line-to-line or line-to-neutral?

Use the line-to-line (phase-to-phase) voltage, which is the voltage measured between any two of the three supply conductors. This is the voltage printed on the motor nameplate. In North America, common 3-phase line-to-line voltages are 208 V, 230 V, 460 V, and 480 V. The formula already includes the sqrt(3) factor to handle the 3-phase geometry; if you instead used the line-to-neutral voltage, you would replace sqrt(3) with 3.

Why does efficiency matter for amperage?

A motor nameplate rating (in hp or kW) is the mechanical output power delivered to the shaft, not the electrical power pulled from the supply. The supply must also deliver the energy lost to heat inside the motor. A motor rated at 10 hp but running at 92% efficiency actually draws 10 / 0.92 = 10.87 hp worth of electrical power. That extra 0.87 hp of losses becomes heat in the windings and core. Higher efficiency means lower FLA for the same output, which translates to smaller conductors and lower operating costs.

How is the minimum conductor size determined?

NEC 430.22 requires that branch-circuit conductors supplying a single motor have an ampacity of at least 125% of the motor FLA. This continuous-load derate prevents the conductor from overheating during sustained operation. Once you know the required ampacity, you look up the smallest conductor size (AWG or kcmil) whose 75 degrees C ampacity rating in a conduit meets or exceeds that value, per NEC Table 310.16. This calculator performs that lookup for copper conductors and shows the result.

Can I use this calculator for motors outside the United States?

The formula for FLA is universal -- it comes from basic AC circuit theory. The conductor-sizing and circuit-breaker results reference NEC Article 430, which is the standard in the United States and Canada. If you are designing a motor installation in Europe or another region, substitute your local standard (for example, IEC 60947-4-1 for motor starters and EN 60204-1 for machine wiring). The calculated FLA itself is still valid regardless of which electrical code applies.