220 Volt Wire Size Calculator

Your details

The continuous current draw of the appliance or circuit in amperes.
A
Distance from panel to load (one way). The calculator doubles this for round-trip resistance.
ft
Aluminum conductors require a larger gauge for the same ampacity as copper.
NEC recommends no more than 3% drop on a branch circuit, 5% combined for feeder + branch. 220V x 3% = 6.6 V.
%
NEC 210.19(A) requires conductors for continuous loads to be sized at 125% of load current (equivalent to 80% of rated breaker capacity).
Minimum wire sizeWithin NEC recommendation
8 AWG

Smallest AWG gauge satisfying both ampacity and voltage-drop limits.

Ampacity-limited gauge8 AWG
Voltage-drop-limited gauge12 AWG
Actual voltage drop2.35V
Actual voltage drop1.07%
Wire diameter3.26mm
Cross-section8.37mm²
Design current used37.5A
1.07 %
NEC recommended<3Marginal3-5Excessive5+

Use 8 AWG copper wire for this 220V circuit.

  • With 8 AWG copper wire, the voltage drop at full load is 2.35 V (1.07% of 220 V).
  • The NEC 125% continuous-load factor has been applied. Your breaker should be rated at least 125% of the load current.
  • Ampacity alone would require 8 AWG, but voltage drop over this run length requires 12 AWG. The larger gauge wins.

Next stepAlways verify the final wire selection with a licensed electrician and confirm it meets local code amendments. NEC is the minimum standard; some jurisdictions are more restrictive.