3-Phase Motor Amperage Calculator

Your details

The rated output power printed on the motor nameplate.
hp
Select the line-to-line supply voltage, or choose Custom to enter a specific value.
Nameplate efficiency as a percentage. Premium-efficiency motors typically fall between 88% and 96%.
%
Ratio of real power to apparent power (dimensionless, 0 to 1). Typical 3-phase induction motors run 0.80 to 0.92 at full load.
Locked-rotor current as a multiple of FLA. Typical induction motors draw 6 to 8 times FLA at start (DOL). Use lower values for soft starters or VFDs.
Full-load amperage (FLA)Medium motor (10-50 A)
11.97A

Steady-state current at rated load

Starting current (LRA)71.8A
Min. conductor size14 AWG
Circuit breaker rating30A
Apparent power (kVA)9.54kVA
Real power input (kW)8.11kW
Full-load (FLA)11.97
Starting (LRA)71.8
Breaker max30

Full-load amperage: 11.97 A at 460 V

  • At 460 V line-to-line and 92% efficiency, your 10 hp motor draws about 11.97 A at full load.
  • The locked-rotor starting current is approximately 71.8 A -- plan your branch circuit accordingly.
  • NEC 430.52 allows a maximum inverse-time circuit breaker of 30 A (250% of FLA). Always verify with your AHJ and the motor nameplate.

Next stepCross-check this FLA against the motor nameplate. The actual rated current can differ from the calculated value due to motor design variations. Always size conductors and protective devices to the nameplate FLA, not the estimated value.